Single-Phase Transformer No-Load Test & Iron Loss Separation
Classified in Physics
Written on in
English with a size of 4.93 KB
Introduction to Transformer No-Load Testing
The no-load test of a transformer is performed by feeding one of its windings with rated voltage and frequency, while the other winding is open-circuited. This test provides the value of iron losses and the no-load current (I0), allowing for the display of its waveform and observation of its characteristic bell shape.
Test Objectives and Fundamentals
Understanding Iron Losses
The power absorbed by a transformer operating under no-load (or vacuum) conditions primarily represents the iron losses, as copper losses are practically negligible due to the small no-load current. Iron losses in a transformer are composed of two main components:
P0: Power absorbed under no-load conditions (total iron losses)PFe: Total iron lossesPH: Hysteresis lossesPF: Eddy current losses
The formulas for these losses are:
PH = kH · Bmx · f
PF = kF · Bm2 · f2
Where:
kHandkFare constants.Bm= Maximum magnetic induction.f= Frequency.- Note: The exponent 'x' for Bm in hysteresis loss typically ranges from 1.6 to 2. Here, we assume it's implicitly handled by kH for simplicity in the separation method.
Therefore, total iron losses can be expressed as:
PFe = PH + PF = kH · f + kF · f2 (assuming Bm is constant)
Separating Hysteresis and Eddy Current Losses
To separate these losses, the transformer, operating under no-load conditions, will be supplied with two different frequencies (e.g., 40 Hz and 60 Hz) to create a system of equations with two unknowns (kH and kF):
PFe(40) = kH · 40 + kF · 402 (Power absorbed at 40 Hz)
PFe(60) = kH · 60 + kF · 602 (Power absorbed at 60 Hz)
Once kH and kF are determined from these equations, the hysteresis losses (PH) and eddy current losses (PF) at the nominal frequency (fn) can be calculated:
PH(fn) = kH · fn
PF(fn) = kF · fn2
The sum of these two components will yield the total iron losses (PFe(fn)) at the nominal frequency, which corresponds to the power absorbed during the no-load test at that frequency.
Maintaining Constant Magnetic Induction
To ensure the maximum magnetic induction (Bm) remains constant at different frequencies, the supply voltage must be adjusted proportionally. This is based on the transformer EMF equation:
E1 = 4.44 · f1 · N1 · S · Bm
Where:
E1: Induced EMF in the primary windingN1: Number of turns in the primary windingf1: Supply frequencyS: Cross-sectional area of the magnetic coreBm: Maximum magnetic induction
If Bm is constant, then the ratio E1 / f1 must be constant. Assuming the supply voltage U is approximately equal to the induced EMF E1, for constant induction, the following relationship must be maintained:
U / f = constant
Therefore, if Un is the nominal voltage at nominal frequency fn (e.g., 50 Hz), then:
Un / fn = U60 / 60 = U40 / 40
Where:
Un: Nominal voltagefn: Rated frequency (e.g., 50 Hz)U60: Supply voltage at 60 HzU40: Supply voltage at 40 Hz
An oscilloscope is used to display the waveform of the no-load current (I0), which is typically non-sinusoidal due to magnetic saturation.
Required Equipment for No-Load Test
- A single-phase transformer
- A true RMS wattmeter (essential for accurate power measurement with highly reactive no-load current)
- An ammeter
- A voltmeter
- An oscilloscope
- A frequency counter
- A variable voltage and frequency power source