Electrical Conductor Specifications and Crossings

Classified in Technology

Written on in English with a size of 3.25 KB

BT06 Bare Conductors Specifications

Breaking Load:
410 daN
Braces and Struts:
1400 daN

Ultimate Safety Factor

  • Metallic: 1.5
  • Reinforced Concrete: 2.5
  • Wood: 3.5
  • Non-metallic: 2.5

1. Isolated Conductors

  • Cables Perched

    • Distance from floor: 2.5m
    • Windows: 0.3m top, 0.5m bottom and sides
    • Balconies: 0.3m top and bottom, 1m sides
  • Tension Cables

    • Ground distance: 4m
    • Mechanical strength: 800 daN

2. Bare Conductors

  • Distance from ground: 4m
  • On the Roof

    • Flat parallel: 1.8m if connected to ground, 1.50m otherwise
    • With inclination of 45 degrees: can be reduced to 1m
  • Terraces and Balconies

    • Flat parallel: 3m
  • Facades

    Protection zone limited to:

    • Plane parallel to the wall at 1m from windows or balconies, further limited by:
      • Plane parallel horizontal top: 0.30m
      • 2 vertical planes, one on each side of the opening: 1m
      • Horizontal plane below sills: 3m

Separation: Bare Conductors & Walls

  • Up to 4m: 0.10m
  • 4m to 6m: 0.15m
  • 6m to 30m: 0.20m
  • 30m to 50m: 0.30m
  • Over 50m: D = 0.55 * √F

Minimum Vertical Distance of Crossings

D = 1.5 + (U + L1 + L2) / 100

3. Crossings

  • Other BT Electric Lines

    • Bare conductors / Different supports: Superior to 0.50m
  • Telecommunications Lines

    • Various supports: 1m
    • Same support: 0.5m
  • Roads and Railways (Non-Electric)

    • Breaking load > 410 daN (bare)
    • Insulated conductors: 280 daN
    • Minimum height: 6m
  • Trolleybuses, Trams, Railways (Electric)

    • Minimum height: 2m
    • Separation: 0.30m (BT conductors)
  • Cable Cars and Carriers

    • BT line: 2m above, 3m below
  • Rivers and Waterways

    • Minimum height: H = 1 + G (if G known), 6m (if G unknown)
  • Radio and TV Reception Antennas

    • Bare conductors: 1m
  • Water and Gas Pipelines

    • Distance between cable: 0.20m

Specific Crossing Requirements

  • With High Voltage Overhead Lines

    • >= 2m (k)
    • 3m minimum (66kV+)
  • With BT Lines or Telecommunications

    • Insulated conductors: 0.1m
    • Bare conductors (on support): can be reduced to 0.5m
  • With Streets and Highways

    • 6m (area)
    • 5m (road traffic)
    • Other cases (bare conductors)
    • Insulated conductors: can be reduced to 4m
  • Rail, Trams, and Trolley

    • 1.5m minimum horizontal distance
  • Water Pipes

    • 0.20m minimum distance
    • 1m away from joints
  • Gas Pipes

    • 0.20m
    • High pressure gas (> 4 bar): 0.40m
    • Distance between cables and bare conductors: 1m (into pipeline)